Runtime Counter

The Runtime Counter enables the implementation of a total operating time measurement and maintenance intervals. Examples are maintenance intervals of filters, runtime detection of motors etc...
As long as Input (En) is On, the time is measured. The total operating time is displayed at the output (To). The interval of the statistics is fixed to 30 minutes.

Table of Contents


Inputs↑

AbbreviationSummaryDescriptionValue Range
EnEnableCounters running while on.0/1
RmcReset maintenance counterResets maintenance counter to parameter Mi.0/1
OffOff / LockPulse (< 200 ms): Outputs are reset / switched off.
Pulse (> 200 ms): Block is locked.
Dominating input.
Pulse (> 500 ms): The name of the connected sensor is used in the user interface.
0/1




Outputs↑

AbbreviationSummaryDescriptionValue Range
MeMaintenance interval exceeded0/1
ToTotal operating time∞
LstLast start time∞
RtmRemaining time maintenanceTime remaining until maintenance interval is reached.∞
APIAPI ConnectorIntelligent API based connector.
Can link several functions between devices and blocks.
API Commands
-




Parameters↑

AbbreviationSummaryDescriptionValue RangeDefault Value
TuTime unit0=seconds
1=minutes
2=hours
3=days
Applies only to the analog outputs, not to the user interface!
0...30
MiMaintenance intervalBlock: Value specified in seconds
Property window: 1d12:00:00.000 (Days, Hours, Minutes, Seconds, Ms)
0 = Output (Me) is not used.
∞0