This bidirectional meter is suitable for recording consumption and delivery of various utilities such as electricity, gas, water, heat, etc.
The values are retrieved from a physical utility meter.
In combination with other meter function blocks, various consumers, producers or storages can be linked via the Energy Flow Monitor for an overall view.
Table of Contents
Inputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
Pf | Power or flow | If only this input is used, the meter reading is also calculated from it. Otherwise it is only used for the output (Pf) and the user interface. |
∞ |
Mrc | Meter reading Consumption | Consumption Input for meters that send the meter reading directly as an analog value. For meters that only send partial quantities (e.g. Smart Socket), relative metering must be activated in the settings of the block. |
0...∞ |
Mrd | Meter reading Delivery | Delivery Input for meters that send the meter reading directly as an analog value. For meters that only send partial quantities (e.g. Smart Socket), relative metering must be activated in the settings of the block. |
0...∞ |
R | Reset | Pulse: Meter reading outputs are reset. On: Block is locked. |
0/1 |
Outputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
Pf | Power or flow | Positive value: Energy is consumed. Negative value: Energy is delivered. |
∞ |
Mrc | Meter Reading consumption | 0...∞ | |
Rdc | Reading today consumption | 0...∞ | |
Rldc | Reading yesterday consumption | 0...∞ | |
Rmc | Reading this month consumption | 0...∞ | |
Rlmc | Reading last month consumption | 0...∞ | |
Ryc | Reading this year consumption | 0...∞ | |
Rlyc | Reading last year consumption | 0...∞ | |
Mrd | Meter Reading delivery | 0...∞ | |
Rdd | Reading today delivery | 0...∞ | |
Rldd | Reading yesterday delivery | 0...∞ | |
Rmd | Reading this month delivery | 0...∞ | |
Rlmd | Reading last month delivery | 0...∞ | |
Ryd | Reading this year delivery | 0...∞ | |
Rlyd | Reading last year delivery | 0...∞ | |
AC | API Connector | Intelligent API based connector. API Commands |
- |
Parameters↑
Abbreviation | Summary | Description | Value Range | Default Value |
---|---|---|---|---|
Mroc | Meter reading offset consumption | Value is added to output (Mrc). | ∞ | 0 |
Mrod | Meter reading offset delivery | Value is added to output (Mrd). | ∞ | 0 |
Properties↑
Summary | Description | Default Value |
---|---|---|
Relative metering | Active: The physical meter only sends partial quantities at intervals (relative), the block adds them up and uses them to form the meter reading. Not active: The physical meter provides its own total meter reading (absolute), the function block only maps it. |
- |
Power/Flow direction | Specifies whether the physical meter provides the delivery or consumption value as a positive or negative value to the Pf input of the block. | - |
Report invalid Meter Reading | When selected, you will be notified if invalid Meter Reading values have been detected. For instance, when a physical counter sends unrealistic values due to transmission errors. | - |
Meter reading and units↑
In general, a physical meter records the quantity and transfers the value to the function block at a meter reading input. The function block maps the meter reading and records the statistics for it.
The units for Pf/Mr can be selected independently of each other, as the value at input Pf is only used for output Pf and for display in the user interface.
If the input Pf is used on its own, the block takes over the function of the meter.
In this case, the units for Pf/Mr must be hour-related and must match in magnitude so that the meter reading is calculated correctly.
Examples:
Pf=kW, Mr=kWh
Pf=W, Mr=Wh
Pf=l/h, Mr=l
Pf=m³/h, Mr=m³
Pf=kg/h, Mr=kg
Detection of Invalid Meter Readings↑
The meter block detects invalid meter readings at the Mr input(s), which can occur due to faulty data transmission from a physical absolute value meter, and ignores them.
In general, only increasing or constant meter readings are allowed; decreasing or jumping to 0 readings are discarded.
Unrealistically high increases in meter readings are discarded if:
-The change in value is greater than the total previous consumption and greater than 10000.
-Only if the time difference since the last value change is less than 8 hours.