RS232

Information on how to install and configure the RS232 Extension

TECHNICAL DATA

  • Connection via Loxone Link
  • 1x RS232 Control Extension
  • Adjustable baud rate
  • Adjustable date format
  • Adjustable protocol
  • Configure with Loxone Config
  • Power supply 24VDC
  • Dimensions: 35.5 x 88 x 57 mm (2 TE)
  • Power consumption approximately 30mA
  • No hardware handshaking
  • Protection: IP20
  • Ambient temperature: 0 to 50°C

Diagram Loxone RS232 Module

INSTALLATION

  • Mount the RS232 Extension on the DIN rail
  • Connect 24VDC power supply, but do not switch on until the whole installation is completed
    (We recommend looping through the Miniserver)
  • Connect the Loxone Link
  • Connect the RS232 Extension to an RS232 device.
  • Note: If it is the last extension, terminate the Loxone Link with a 120Ω resistor (Included with the Miniserver)
  • Turn on the power supply
  • After a few seconds, the left LED will flash green if the extension is already configured, or orange if not

DIMENSIONS

Diagram Loxone RS232 Module Dimensions

CONFIGURING EXTENSIONS

Click here to find out how

SETTING UP A FRONIUS SOLAR INVERTER

The values from a Fronius Inverter can be read using Fronius’s RS232 Converter Box and Loxone’s RS232 Extension.

SELECT THE PROTOCOL

Connection Parameters:
Auto-baud rate (2400, 4800, 9600, 14400, 19200), 8 data bits, 1 stop bit.
In order for the sensor values to be transmitted, you must select the ‘Fronius’ protocol.

Loxone RS232 Fronius

CHANGE ID IN THE SETUP MENU

The inverter responds only to a value-request. These requests are saved in the actuators, therefore a pulse at the actuator writes the current value to the corresponding sensor.
In this request-command the inverter’s ID is included (which can be changed in the setup menu). By default, a request-command saves the ID 01.

Loxone RS232 Actuators

Icon Exclamation Mark Loxone
The following measured values are sent with decimal places. The decimal places falsify the measured values to the power of 2 or 3 respectively:

2 Decimal Places:
Get Yield – DAY
Get Yield – YEAR
Get Yield – TOTAL

1 Decimal Place:
Get operating Hours – DAY

These sensor values can be corrected by the divider function block. Please note that the operating time is given in minutes.