Fire Pump Control

  • Country NO, Sogndal
  • Build year 2022
  • Area 15 m2 m²
  • LOXONE partner Systemintegrering AS
Fire Pump Control

Challenge

Controlling an 100A pump that supplies a Fire hydrant system at a Business park.

The premesis:

Nightlight controll

Frost protection, by oven.

Get a constant pressure of 5 Bar on the output.

Automatic Maintenance each month; run the pump for 5-10 seconds.

Shutdown when there is no wather on the pump input.

Sentral control panel for ajusting setpoint for pressure, times and heating.

Solution

I used a Miniserver Gen 1 due to the amount of Analoge out/ and inputs.

Pressure sensor on intake and output on the pump.

0-10V signal to the frequency converter, and relay output for controlling Start and Frequency/engine speed.



Additional Start/Stop buttons for easy access.