Ceiling Light Pure RGBW Air

The LOXONE Ceiling Light Pure RGBW Air is a downlight with an integrated presence detector and brightness sensor that combines high-quality white light from 2 200 K to 6 500 K with vibrant colored light. Control and dimming are handled directly via the integrated Air interface.

Datasheet Ceiling Light Pure 12 RGBW Air

Datasheet Ceiling Light Pure 17 RGBW Air

Table of Contents


Mounting↑

Mount the ceiling mounting base and connect the power supply (orange/orange-white terminal).

Hang the light fixture from the ceiling mounting base using the steel cable.

The steel cable serves as a safety cable and must not be removed!

Then plug in the connector between the luminaire and the ceiling mounting base.

Align the three magnets with the flat areas of the ceiling plate. Push the luminaire upwards and turn it until it locks into place. Make sure the markings are aligned and no wires are pinched between the magnets.


Commissioning↑

For commissioning, the device must be supplied with power and a connection to the Miniserver must be possible via the Air Interface.

Then follow the pairing procedure on the Air Interface.

To manually activate pairing mode, disconnect the device from the power supply for 10 seconds and then power it on again. If no connection to the Miniserver can be established within two minutes, pairing mode is activated for 30 minutes.


Sensors↑

SummaryDescriptionUnitValue Range
Volume MinimumProvides the minimum volume periodically based on the value set in "Volume Transmission Cycle".-20...2000
Volume MaximumProvides the maximum volume periodically based on the value set in "Volume Transmission Cycle".-20...2000
BrightnessProvides the measured value of the current brightness. Value is not updated when the light is onLx∞
MotionInput is active when motion is detected-0/1
PresenceInput is active as long as presence is detected. Motion activates the input, volume and motion keep it active.-0/1
Sound level alarmInput provides a pulse when the volume exceeds the threshold for the sound level alarm. 1 pulse per 10s.-0/1




Actuators↑

SummaryDescriptionValue Range
Smart ActuatorThe minimum fading time is 1s.∞




Diagnostic Inputs↑

SummaryDescriptionUnitValue Range
Online Status Ceiling Light Pure RGBW AirIndicates whether the device can be reached by the Miniserver.
Diagnostics for Air devices
Diagnostics for Tree devices
Diagnostics for Extensions
Digital0/1
System temperatureProvides the internal device temperature.
This is often the temperature of the CPU or another location in the device.
°∞
Temperature ShutdownInput is active, when the outputs of the device have been switched off due to high device temperature. Possible reasons: Ambient temperature too high, outputs overloaded.Digital0/1




Properties↑

SummaryDescriptionUnitValue RangeDefault Value
Monitor online statusIf checked, you will be notified via System Status or the Mailer if the device is no longer available or goes offline.---
Disable Repeater functionalityDisable repeater functionality of this Air device.

LOXONE Air is based on mesh technology. Any air device connected to the power supply can repeat packets from other Air devices, thus extending the range and stability of the overall system.
In large systems with a large number of air devices in a confined space, the communication between the air devices can lead to a very high radio channel utilization. A reliable accessibility of the air devices can not be guaranteed. Disabling repeater functionality on individual Air devices can help.

Do not disable this function recklessly as this may affect the range and stability of the system.
---
Serial numberSerial number of Air device.
Automatic pairing can be enabled on the Air Base.

Automatic pairing can be enabled on the Airbase for a set time.
---
Lighting GroupAssigned Lighting Group. To create a new group simply start typing a name.---
Volume threshold presenceMinimum sound level to detect presence-20...2000250
Volume threshold sound level alarmMinimum volume to trigger sound level alarm-20...20001000
Volume thresholdsConfigure the volume thresholds using a graph of the current volume---
Overrun time presenceOverrun time for presence input.s2...60000300
Overrun time motionThe 'Motion (Mo)' input remains active following the last detected motion for the set time. A higher value means less packets have to be sent via Tree and Link.
If the motion detector is used for the alarm system, the time is automatically set to 3 seconds when the alarm system is armed.
s2...90060
Volume transmission cycleTransmission cycle for minimum and maximum volume (1-3600 sec, 0=off)s0...3600300
Brightness transmission cycleThe brightness is transmitted periodically at the set transmission cycle (0=OFF). In addition, the brightness is transmitted when presence is detected or when there is a change of at least 30%. If the brightness is used by a Constant Brightness Controller, it is transmitted at a change of 5%.s0...7200900
Presence duration without motionPresence ends when no motion has been detected for this duration.
This prevents constant ambient noise from keeping presence active.
Before using this function, check if the volume threshold for presence is set accordingly.
0 = Disables this function.
s0...600001800
SensitivityEffects the sensitivity and thus also the distance over which motion can be sensed---



Safety Instructions↑

Installation must be carried out by a qualified electrician in accordance with the applicable regulations.


Documents↑

Datasheet Ceiling Light Pure 12 RGBW Air

Datasheet Ceiling Light Pure 17 RGBW Air