AI Extension

The AI Extension features 4 inputs for analog voltage signals like 0-10V or digital, as well as 4 analog inputs for current signals like 0/4-20mA.

The inputs AI1-AI4 for voltage signals operate differentially, each with two terminals for signal and reference potential. The integrated open-wire detection detects interruptions in the measuring circuit.

The inputs AI5-AI8 for current signals work passively, and can be integrated into current loops.

All inputs can also measure negative values with reversed polarity.

All inputs are galvanically isolated from the supply side of the Extension.

Datasheet AI Extension

Table of Contents


Commissioning

The Extension is installed on a DIN rail in a suitable enclosure.

Connect the power supply and the link data lines to the Miniserver.

The lines for voltage signals are connected to the analog inputs AI1 to AI4. The GND (negative pole) of the associated signal is also required at each input.

The analog inputs AI5 to AI8 are integrated in current loops.

The Extension starts after switching on the power supply, and the status LED will flash orange after a short time when the connection to the Miniserver is established.

Then follow the pairing procedure on the Link Interface.


Connecting Analog Inputs

Connection examples 0-10V

0-10V transmitter with 2 outputs:

Connection examples 4-20mA

Active 4-20mA transmitter:

Passive 4-20mA transmitter:


Sensors

SummaryUnitValue Range
Voltage 1V
Voltage 2V
Voltage 3V
Voltage 4V
Current 1mA
Current 2mA
Current 3mA
Current 4mA




Diagnostic Inputs

SummaryDescriptionUnitValue Range
Online Status AI ExtensionIndicates whether the device can be reached by the Miniserver.
Diagnostics for Air devices
Diagnostics for Tree devices
Diagnostics for Extensions
Digital0/1
Open Wire 1Digital0/1
Open Wire 2Digital0/1
Open Wire 3Digital0/1
Open Wire 4Digital0/1




Properties

SummaryDescriptionDefault Value
Serial numberSpecifies the serial number of the device.

Enter 'Auto' to automatically pair an Extension with unknown serial number.
This can only be used if there is only one Extension of the same type on a standalone Miniserver (not in a Client-Gateway setup).
Save in the Miniserver to pair the Extension.
Afterwards the program must be loaded from the Miniserver to transfer the actual serial number of the Extension into the program.
-
Monitor online statusIf checked, you will be notified via System Status or the Mailer if the device is no longer available or goes offline.-



Safety Instructions

Installation must be carried out by a qualified electrician in accordance with the applicable regulations.

This device must be mounted on a DIN rail in an electrical distribution enclosure to ensure protection against contact, water and dust.


Documents

Datasheet AI Extension