The LOXONE Touch Pure Display provides intuitive room control in a single device. The human-centered touch interface allows control of lighting, shading, audio, and other functions.
When not in use, the display enters Rest Mode, allowing it to be turned off completely or to show essential room information such as temperature.
Datasheet Touch Pure Display Tree
Datasheet Touch Pure Display CO2 Tree
Table of Contents
- Mounting
- Commissioning
- CO2 Sensor
- Wi-Fi
- Programming
- Inputs, Outputs, Properties
- Safety Instructions
- Documents
Mounting↑
Attach the supplied plastic mounting frame to a flat surface or an installation box. For flush-mounted installations, a 68 mm flush-mount box is recommended.
A device box is not strictly necessary but is highly recommended, as it greatly simplifies storing the connection cables behind the device and creating a reserve loop.
![]() | Recommended mounting height: 1.45 m |

Connect the power supply (orange/white terminal) and the LOXONE Tree data lines (green/white terminal).
Insert the device into the top of the mounting frame and snap it into place at the bottom.

![]() | Please note that the Touch Pure Display does not fit into old mounting frames. |
Commissioning↑
For commissioning, the device must be supplied with power and a connection to the Miniserver must be possible via the Tree Interface.
Then follow the pairing procedure on the Tree Interface.
CO2 Sensor↑
Within the first 12 hours after power-up, the CO2 sensor will automatically calibrate itself for the first time. During this period, sensor readings may not be accurate. The CO2 sensor recalibrates itself over time, assuming exposure to fresh air (approx. 400 ppm CO2) at least once per week.
Wi-Fi↑
In the properties window, Wi‑Fi can be enabled for this device. Enter the SSID and password of your network.
Some functionality is only available with an active Wi‑Fi connection, e.g., intercom and additional audio features.

![]() | This device is restricted to indoor use only when operating in the 5150 to 5350 MHz frequency range in: AT, BE, BG, CY, CZ, DE, DK, EE, EL, ES, FI, FR, HR, HU, IE, IT, LT, LU, LV, MT, NL, PL, PT, RO, SE, SI, SK, IS, LI, NO, CH. The device is also restricted to indoor use in the United Kingdom. |
Programming↑
The Touch Pure Display is programmed and set up using the Touch Pure Display Controller function block in LOXONE Config:

Sensors↑
| Summary | Description | Unit | Value Range |
|---|---|---|---|
| Temperature | Measured value of the temperature sensor. | ° | -40...125 |
| Humidity | Measured value of the humidity sensor. | % | 0...100 |
| CO2 | Measured CO2 value. | ppm | - |
Actuators↑
| Summary | Description | Unit | Value Range |
|---|---|---|---|
| Backlight | Output to control the backlight. | % | 0...100 |
| Volume | % | ∞ | |
| Orientation light | Digital | 0/1 | |
| API Connector | Intelligent API based connector. API Commands | - | - |
Diagnostic Inputs↑
| Summary | Description | Unit | Value Range |
|---|---|---|---|
| Online Status Touch Pure Display Tree | Indicates whether the device can be reached by the Miniserver. Diagnostics for Air devices Diagnostics for Tree devices Diagnostics for Extensions | Digital | 0/1 |
Properties↑
| Summary | Description | Unit | Value Range | Default Value |
|---|---|---|---|---|
| Monitor online status | If checked, you will be notified via System Status or the Mailer if the device is no longer available or goes offline. | - | - | - |
| Serial number | Specifies the serial number of the device. Enter 'Auto' to automatically pair a Tree device with unknown serial number. This can only be used if there is only one Tree device of the same type on a standalone Miniserver (not in a Client-Gateway setup). Save in the Miniserver to pair the Tree device. Afterwards the program must be loaded from the Miniserver to transfer the actual serial number of the Tree device into the program. | - | - | - |
| Send interval | Send interval in seconds for each of the three sensors (temperature, humidity, CO2). 0 = Automatic | min | 0...4294967295 | 0 |
Safety Instructions↑
Installation must be carried out by a qualified electrician in accordance with the applicable regulations.
Documents↑
Datasheet Touch Pure Display Tree
Datasheet Touch Pure Display CO2 Tree