Touch Pure Tree

The Loxone Touch Pure Tree features five touch points on a glass surface to control the most important functions of a room. When a button is touched, an audible click confirms the action.

The large center touch zone is ideal for controlling the lighting, while the corner zones are suitable for controlling music and shading. It is based on the Loxone switch standard. The buttons can also be freely used for other applications.

It also features a controllable orientation light and the integrated sensor measures temperature and relative humidity.

Please note that there is a certain delay when measuring humidity due to the housing. The Room Comfort Sensor is better suited for a fast detection of changes in humidity.

Datasheet Touch Pure Tree

Table of Contents


Mounting

Install the mounting frame at the desired location.

Connect the power supply (orange/white terminal) and Tree communication wires (green/white terminals). Shortly after power-up, the status LED will blink orange if the wiring is correct (connection to Tree Extension and Miniserver is established).

Mount the device by snapping it onto the mounting frame.


Commissioning

Then follow the pairing procedure on the Tree Interface.


Sensors

Summary Description Unit Value Range
T5 Combined input for the 5 touch points according to the Loxone Switch Standard. -
Temperature Provides the air temperature. ° -40...125
Humidity Provides the air humidity. % 0...100




Actuators

Summary Description Value Range
Orientation light Digital output to control the orientation light. 0/1




Diagnostic Inputs

Summary Description Unit Value Range
Online Status Touch Pure Tree Indicates whether the device can be reached by the Miniserver.
Diagnostics for Air devices
Diagnostics for Tree devices
Diagnostics for Extensions
Digital 0/1




Properties

Summary Description Default Value
Monitor Online Status When selected, you will be notified via System Status or the Mailer if the device is no longer available or goes offline. -
Serial Number Specifies the serial number of the device.
For Extensions: Enter 'Auto' to automatically pair an extension with unknown serial number.
This can only be used if there is only one Extension of the same type.
Save into the Miniserver, in order to pair the Extension.
Afterwards the program must be loaded from the Miniserver to transfer the actual serial number of the Extension into the program.
-
Device type Tree device type -
Show Button 1 Show individual button -
Show Button 2 Show individual button -
Show Button 3 Show individual button -
Show Button 4 Show individual button -
Show Button 5 Show individual button -
Audible acknowledgement Audible acknowledgement on button press -




Safety Instructions

The installation must be carried out by a qualified technician in accordance with all applicable regulations.

Ensure that the device is protected from water.

The device must not be used as part of safety-critical systems.