Touch Pure Display Air

The LOXONE Touch Pure Display provides intuitive room control in a single device. The human-centered touch interface allows control of lighting, shading, audio, and other functions.

When not in use, the display enters Rest Mode, allowing it to be turned off completely or to show essential room information such as temperature.

Datasheet Touch Pure Display Air

Datasheet Touch Pure Display CO2 Air

Table of Contents


Mounting

Attach the supplied plastic mounting frame to a flat surface or an installation box. For flush-mounted installations, a 68 mm flush-mount box is recommended.
A device box is not strictly necessary but is highly recommended, as it greatly simplifies storing the connection cables behind the device and creating a reserve loop.

Recommended mounting height: 1.45 m

Insert the device into the top of the mounting frame and snap it into place at the bottom.

Please note that the Touch Pure Display does not fit into old mounting frames.

Commissioning

For commissioning, the device must be supplied with power and a connection to the Miniserver must be possible via the Air Interface.

Then follow the pairing procedure on the Air Interface.

To manually activate pairing mode, press the pairing button on the display after powering the device.


CO2 Sensor

Within the first 12 hours after power-up, the CO2 sensor will automatically calibrate itself for the first time. During this period, sensor readings may not be accurate. The CO2 sensor recalibrates itself over time, assuming exposure to fresh air (approx. 400 ppm CO2) at least once per week.


Wi-Fi

In the properties window, Wi‑Fi can be enabled for this device. Enter the SSID and password of your network.
Some functionality is only available with an active Wi‑Fi connection, e.g., intercom and additional audio features.

This device is restricted to indoor use only when operating in the 5150 to 5350 MHz frequency range in: AT, BE, BG, CY, CZ, DE, DK, EE, EL, ES, FI, FR, HR, HU, IE, IT, LT, LU, LV, MT, NL, PL, PT, RO, SE, SI, SK, IS, LI, NO, CH.
The device is also restricted to indoor use in the United Kingdom.

Programming

The Touch Pure Display is programmed and set up using the Touch Pure Display Controller function block in LOXONE Config:


Sensors

SummaryDescriptionUnitValue Range
TemperatureMeasured value of the temperature sensor.°-40...125
HumidityMeasured value of the humidity sensor.%0...100
CO2Measured CO2 value.ppm-




Actuators

SummaryDescriptionUnitValue Range
BacklightOutput to control the backlight.%0...100
Volume%
Orientation lightDigital0/1
API ConnectorIntelligent API based connector.
API Commands
--




Diagnostic Inputs

SummaryDescriptionUnitValue Range
Online Status Touch Pure Display AirIndicates whether the device can be reached by the Miniserver.
Diagnostics for Air devices
Diagnostics for Tree devices
Diagnostics for Extensions
Digital0/1




Properties

SummaryDescriptionUnitValue RangeDefault Value
Monitor Online StatusIf checked, you will be notified via System Status or the Mailer if the device is no longer available or goes offline.---
Serial NumberSerial number of Air device.
Automatic pairing can be enabled on the Air Base.

Automatic pairing can be enabled on the Airbase for a set time.
---
Send intervalSend interval in seconds for each of the three sensors (temperature, humidity, CO2). 0 = Automaticmin0...42949672950



Safety Instructions

Installation must be carried out by a qualified electrician in accordance with the applicable regulations.