The Smoke & Presence Detector Tree combines a presence sensor and a smoke detector in a single device. It provides optical smoke detection according to EN 14604 for early fire warning, along with reliable detection of presence, motion, and brightness.
![]() | The integrated presence sensor can also detect some pets. Although the sensitivity of the sensor can be reduced, there is no dedicated technology that excludes the detection of pets. |
Datasheet Smoke & Presence Detector Tree White / Anthracite
Table of Contents
- Mounting Position & Planning
- Mounting
- Commissioning
- Signal Overview
- Function Test
- Interconnected Smoke Detector
- Motion Detection Range & Placement
- Set volume thresholds
- False Alarm
- Battery Replacement
- Programming Example
- Inputs, Outputs, Properties
- Safety Instructions
- Documents
Mounting Position & Planning↑
![]() | The installation of smoke detectors must comply with all country-specific regulations and standards. |
For optimal protection, install multiple smoke detectors throughout the building.
![]() | For reliable motion detection by the integrated presence sensor, correct placement on the ceiling is also essential. For more information, see the section Motion Detection Range & Placement. |
If possible, smoke detectors should be mounted centrally on the ceiling, at least 0.5 m (1.64 ft) away from walls, beams, or furniture that could obstruct the entry of smoke.
In hallways up to 3 m (9.84 ft) wide, the maximum spacing between two smoke detectors should not exceed 15 m (49.21 ft). The distance from the smoke detector to the end of the hallway should be no more than 7.5 m (24.6 ft). Smoke detectors must also be installed at intersections, junctions, and corners.
If a room is divided by a gallery, platform or loft, a smoke detector must be installed below it if the platform is larger than 16 m² (172.22 ft²) and both length and width are greater than 2 m (6.56 ft).
Ceiling structures such as beams or suspensions that create separate ceiling areas must also be taken into account. If the height of these structures exceeds 0.2 m (0.66 ft) and the resulting ceiling area is larger than 36 m² (387.50 ft²), a smoke detector must be installed in each section.

| Yes |
| Not mandatory! Recommended for optimal protection |
| Recommendation: Use Smoke & Presence Detector as a heat detector |
Mounting on Sloped Ceilings
The smoke detector can be mounted on the ceiling or wall, with ceiling mounting being preferred. A minimum distance of 0.5 m (1.64 ft) from any obstacles must be observed.

Mounting↑
First, insert the supplied 9 V battery into the device.
![]() | A battery is essential for operation. Installation without a battery is not possible. |

Secure the supplied plastic base to a flat surface using screws.
![]() | To prevent air draft, the installation conduit should be sealed airtight. |

Connect the power supply (orange/white terminal) and the Tree data lines (green/white terminal).
Place the detector onto the base and turn it clockwise until it clicks securely into place.

After that, switch on the power supply. Once the detector is successfully connected to the Miniserver, it will flash orange shortly after. The detector is then ready for pairing.
Commissioning↑
In the delivery state, pairing mode is active as soon as the power supply is established, the battery is inserted, and the device is mounted onto the base.
Then follow the pairing procedure on the Tree Interface.
![]() | If the detector is not mounted correctly, the LED will flash orange/red after programming. Additionally, in Loxone Config, a message will be displayed indicating that the device has been removed. |
Signal Overview↑
Smoke Detection
| Status | Sound Signal | Smoke Detector LED |
|---|---|---|
| Normal operation | off |
|
| Smoke alarm | 3 beeps every 4 s |
|
| Heat alarm | 4 beeps every 5 s |
|
| Other alarm | 5 beeps every 6 s |
|
| Fault | 2 beeps every 60 s |
|
| Low battery | 1 beep every 60 s |
|
| Alarm silenced | off |
|
| Function test (while housing is pressed) | continuous tone |
|
Loxone Status
| Status | Sound Signal | Tree Status LED |
|---|---|---|
| Normal operation | off |
|
| Connected but not configured | off |
|
| Device is being identified in Loxone Config | rapidly alternating beeps |
|
| Device not mounted | off |
|
Function Test↑
1. Press and hold the entire housing to activate the function test.
2. After approx. 3 s, an acoustic signal will sound and will continue as long as the housing is pressed.
If the device is functioning properly, the signal will stop once the device is released.
In case of a fault, the error signal will sound and repeat every minute.
Possible causes: low battery, sensor fault

Extended Function Test (with Test Gas)
To perform an extended function test with test gas (e.g., smoke spray), the service mode must first be activated.
Press and hold the housing for more than 3 s to trigger the function test. The service mode will be active for 60 s.
During this time, the detector can be tested with test gas.
Interconnected Smoke Detector↑
Smoke and presence detectors on the same Tree branch are directly interconnected. If one detector detects smoke, all detectors on the branch immediately sound an alarm. The alarm is forwarded device-to-device, without going through the Miniserver.
Up to 50 Smoke and Presence Detectors can be connected to each Tree branch, with a maximum branch cable length of 500 m (1640 ft).
The Interconnect function is certified. In many jurisdictions this type of interconnected alarm system is required, ensuring all detectors trigger together even without a central controller.
When an alarm is triggered by the Miniserver, all Tree Smoke and Presence Detectors and all Air detectors supplied by 24V power supply also trigger an alarm.
Motion Detection Range & Placement↑
For reliable motion detection, correct placement of the Smoke & Presence Detector on the ceiling is essential. The following illustrations show typical detection ranges depending on the mounting height.
Sensitivity does not define a fixed detection boundary, but adjusts internal parameters that influence range and responsiveness.
To selectively exclude areas or define specific detection zones, use the stickers included in the package.


Set volume thresholds↑
In the properties window, a diagram for configuring threshold values can be opened under "Volume thresholds".

The diagram is based on the current ambient sound level of the selected Smoke & Presence Detector and supports the adjustment of the thresholds for presence and sound alarm. Temporary noise sources such as dishwashers, construction noise, or traffic noise must also be taken into account.
False Alarm↑
CAUTION: Smoke, dust, steam, electromagnetic interference, condensation, and insects can cause false triggers.

CAUTION: Drafts can affect smoke detection.

After a false alarm, clean the device with a dry cloth and perform a function test.
Battery Replacement↑
1. Remove the detector from the base by turning it counterclockwise.
2. Replace the 9 V lithium battery with the recommended battery.

3. Reattach the detector to the base by turning it clockwise.
4. Perform a function test.
![]() | CAUTION: There is a risk of explosion if the battery is replaced improperly. The replacement must only be with the same or specified type. Do not expose the battery to heat, fire, or direct sunlight. Do not recharge, short-circuit, or open the battery. Dispose of the used battery in accordance with local regulations. |
Programming Example↑
Double-click the Fire and Water Alarm function block to select the inputs and outputs of the smoke detector.

Alternatively, the inputs and outputs can be manually dragged onto the programming page. For example, the inputs "Brightness" and "Presence" can be used with the Lighting Controller.

Sensors↑
| Summary | Description | Unit | Value Range |
|---|---|---|---|
| Volume minimum | Provides the minimum volume periodically based on the value set in "Volume Transmission Cycle". Not available when battery operated. | - | 20...2000 |
| Volume maximum | Provides the maximum volume periodically based on the value set in "Volume Transmission Cycle". Not available when battery operated. | - | 20...2000 |
| Brightness | Measured value of the current brightness | Lx | 0...83000 |
| Fire alarm | - | 0/1 | |
| Motion | Input is active when motion is detected | - | 0/1 |
| Presence | Input is active as long as presence is detected. Motion activates the input, volume and motion keep it active. Not available when battery operated. | - | 0/1 |
| Sound level alarm | Input provides a pulse when the volume exceeds the threshold for the sound level alarm. 1 pulse per 10s. Not available when battery operated. | - | 0/1 |
| Temperature | ° | ∞ |
Diagnostic Inputs↑
| Summary | Description | Unit | Value Range |
|---|---|---|---|
| Online Status Smoke and Presence Detector Tree | Indicates whether the device can be reached by the Miniserver. Diagnostics for Air devices Diagnostics for Tree devices Diagnostics for Extensions | Digital | 0/1 |
| Battery level | Provides the current battery level. | % | 0...100 |
| Battery low | Indicates low battery, battery needs to be replaced. | - | 0/1 |
| Test button | - | 0/1 | |
| End of life | - | 0/1 | |
| Device removed | - | 0/1 | |
| Fault detected | - | ∞ |
Actuators↑
| Summary | Unit | Value Range |
|---|---|---|
| Bell sound | Digital | 0/1 |
Properties↑
| Summary | Description | Unit | Value Range | Default Value |
|---|---|---|---|---|
| Monitor Online Status | You will be notified via System Status or Could Mailer if the device is no longer available or offline. As this device and it's functionality are critical to safety, it is not possible to disable this setting for this device. | - | - | - |
| Serial Number | Specifies the serial number of the device. Enter 'Auto' to automatically pair a Tree device with unknown serial number. This can only be used if there is only one Tree device of the same type on a standalone Miniserver (not in a Client-Gateway setup). Save in the Miniserver to pair the Tree device. Afterwards the program must be loaded from the Miniserver to transfer the actual serial number of the Tree device into the program. | - | - | - |
| Fire alarm detection mode | Specifies whether the smoke detector triggers a fire alarm in response to smoke, heat, or both. | - | - | - |
| Enable Interconnection | If checked, this detector communicates with other detectors on the same Tree branch. Interconnected detectors on the same Tree branch will trigger alarms simultaneously in the event of a fire. | - | - | - |
| Presence Volume Threshold | Minimum sound level to detect presence | - | 20...2000 | 250 |
| Sound Level Alarm Volume Threshold | Minimum volume to trigger sound level alarm | - | 20...2000 | 1000 |
| Volume thresholds | Configure the volume thresholds using a graph of the current volume | - | - | - |
| Overrun Time Presence | Overrun time for presence input. | s | 2...60000 | 300 |
| Overrun time motion | The 'Motion (Mo)' input remains active following the last detected motion for the set time. A higher value means less packets have to be sent via Tree and Link. If the motion detector is used for the alarm system, the time is automatically set to 3 seconds when the alarm system is armed. | s | 2...900 | 60 |
| Volume Transmission Cycle | Transmission cycle for minimum and maximum volume (1-3600 sec, 0=off) | s | 0...3600 | 300 |
| Brightness transmission cycle | The brightness is transmitted periodically at the set transmission cycle (0=OFF). In addition, the brightness is transmitted when presence is detected or when there is a change of at least 30%. If the brightness is used by a Constant Brightness Controller, it is transmitted at a change of 5%. | s | 0...7200 | 900 |
| Presence duration without motion | Presence ends when no motion has been detected for this duration. This prevents constant ambient noise from keeping presence active. Before using this function, check if the volume threshold for presence is set accordingly. 0 = Disables this function. | s | 0...60000 | 1800 |
| Sensitivity | Effects the sensitivity and thus also the distance over which motion can be sensed | - | - | - |
Safety Instructions↑
Installation must be carried out by a qualified electrician in accordance with the applicable regulations and fire safety standards. Use only as intended. For indoor use only. Not suitable for habitable recreational vehicles. Improper use may result in property damage or injury.
Replace the device 10 years after initial activation.
Documents↑
Datasheet Smoke & Presence Detector Tree White / Anthracite