Selection Switch (+)

A pulse on input (+) increases the value on output (O) by the step size (Sts). When (Vmax) is reached, it starts again at (Vmin).
A long-click on (+) increases the value on output (O) every (Rr) seconds.

Table of Contents


Inputs↑

AbbreviationSummaryDescriptionValue Range
+Value+Increases the value at output (O) by the step size (Sts). When (Vmax) is reached, it starts again at (Vmin).0/1
ValSet valueSets a specific value on output (O).∞
OffOff / LockPulse (< 200 ms): Output (O) is reset to the default value (Vdef).
Pulse (> 200 ms): Block is locked.
Dominating input.
Pulse (> 500 ms): The name of the connected sensor is used in the user interface.
0/1
DisPcDisable periphery controlDisables all inputs when On. (e.g Child lock, cleaning)
Control via user interface is still possible.
0/1




Outputs↑

AbbreviationSummaryDescriptionValue Range
OOutput∞
APIAPI ConnectorIntelligent API based connector.
Can link several functions between devices and blocks.
API Commands
-




Parameters↑

AbbreviationSummaryDescriptionUnitValue RangeDefault Value
RemRemanence inputRemanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
-0/10
VminMinimum value-∞1
VmaxMaximum value-∞10
StsStep size-∞1
RrRepetition rateLong-click on (+) increases the value on output (O) every (Rr) seconds.s0...∞0,2
VdefDefault valueDefault value when input (Off) is triggered.-∞1



Timing Diagram↑