Pulse Meter Bidirectional

This bidirectional meter is suitable for recording consumption and delivery of various utilities such as electricity, gas, water, heat, etc.

The values are retrieved from a physical utility meter with pulse output (S0).

In combination with other meter function blocks, various consumers, producers or storages can be linked via the Energy Flow Monitor for an overall view.

Table of Contents


Inputs

AbbreviationSummaryDescriptionValue Range
PcPulse consumptionFor meters with pulse output (S0), connected to digital inputs.0/1
PdPulse deliveryFor meters with pulse output (S0), connected to digital inputs.0/1
FcFrequency consumptionFor meters with pulse output (S0), connected to digital inputs used as frequency counter.0...∞
FdFrequency deliveryFor meters with pulse output (S0), connected to digital inputs used as frequency counter.0...∞
RResetPulse: Meter reading outputs are reset.
On: Block is locked.
0/1




Parameters

AbbreviationSummaryDescriptionValue RangeDefault Value
NpcNumber of pulses per unit0...∞1000
NpdNumber of pulses per unit0...∞1000
MrocMeter reading offset consumptionValue is added to output (Mrc).0
MrodMeter reading offset deliveryValue is added to output (Mrd).0




Outputs

AbbreviationSummaryDescriptionValue Range
PfPower or flowCurrent power/flow calculated using inputs (Pc) and (Fc) is output as a positive value.
Current power/flow calculated using inputs (Pd) and (Fd) is output as a negative value.
MrcMeter Reading consumption0...∞
RdcReading today consumption0...∞
RldcReading yesterday consumption0...∞
RmcReading this month consumption0...∞
RlmcReading last month consumption0...∞
RycReading this year consumption0...∞
RlycReading last year consumption0...∞
MrdMeter Reading delivery0...∞
RddReading today delivery0...∞
RlddReading yesterday delivery0...∞
RmdReading this month delivery0...∞
RlmdReading last month delivery0...∞
RydReading this year delivery0...∞
RlydReading last year delivery0...∞
APIAPI ConnectorIntelligent API based connector.
API Commands
-




Properties

SummaryDescriptionDefault Value
Report invalid Meter ReadingIf checked, you will be notified if invalid Meter Reading values have been detected. For instance, when a physical counter sends unrealistic values due to transmission errors.-



Meter reading and units

The physical meter provides a certain number of pulses per unit of quantity, this must be set at parameter (Np). The block uses this to form the meter reading (Mr), calculates the power or flow rate (Pf), and records the statistics.

The units for Pf/Mr must be hour-related and must match in magnitude so that Pf is calculated correctly.
Examples:
Pf=kW, Mr=kWh
Pf=W, Mr=Wh
Pf=l/h, Mr=l
Pf=m³/h, Mr=m³
Pf=kg/h, Mr=kg