Dimmer

Optimised dimmer with double click function for single button operation.

Table of Contents


Inputs

Abbreviation Summary Description Value Range
Tg Toggle Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1).
Long-click for dimming up/down.
0/1
+ Dim+ Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1).
Long-click for dimming up.
0/1
- Dim- Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1).
Long-click for dimming down.
0/1
Off Off Pulse: Outputs are reset / switched off.
On: Block is locked.
Dominating input.
The name of the connected sensor is used in the user interface.
0/1
DisPc Disable periphery control Disables inputs (Tg), (+), (-) when On. (e.g Child lock, cleaning)
Control via user interface is still possible.
0/1
Set Sets output (D) to value of input (Set)




Outputs

Abbreviation Summary Description Value Range
D Dimmer output Analog output for dimmer control (e.g. 0-10V)
S Status On when output (D) is greater than 0. 0/1
API API Connector Intelligent API based connector.
API Commands
-




Parameters

Abbreviation Summary Description Value Range Default Value
Rem Remanence input Remanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
0/1 0
Di Delay input Delays input for set time. If this parameter is set too low, the block may interpret the input as a held button press rather than a normal (short) click.
Applies to inputs (Tg), (+), (-).
0,4
Sts Step size 0,5
Str Step rate Dim value is in-/decreased by (Sts) every (Str) seconds on long-click. 0,2
MinD Minimum dim value 0
MaxD Maximum dim value 100
Dm Dim mode 1 = Dim between parameters (MinD) and (MaxD) on long-click.
0 = Stop dimming when reaching parameter (MinD) or parameter (MaxD) on long-click.
Only applies to input (Tg).
0/1 0
Lv Last value 1 = Sets output (D) to (MaxD) when switching on.
0 = Sets last value to ouput (D) when switching on.
0/1 0




Presence Simulation

This function block has a presence simulation.
Activate and define the presence simulation in the properties window: