Toilet Ventilation Controller

The Toilet Ventilation Controller works in "Sessions". A pulse at the input (Tg) will start or end the session.
Output (S) is switched on directly after being triggered. Output (Fan) switches on after the delay set in Parameter (Fsd).
If input (P) is used, the session starts with a rising edge at input (P) and ends the session at a falling edge, delayed by the duration set in parameter (FPet).

Table of Contents


Inputs

AbbreviationSummaryDescriptionValue Range
TgToggleStart / end session.0/1
PPresenceStart session when 1.0/1
OffOffPulse: Outputs are reset / switched off.
On: Block is locked.
Dominating input.
0/1
DisPcDisable periphery controlDisables all inputs when On. (e.g Child lock, cleaning)
Control via user interface is still possible.
0/1




Outputs

AbbreviationSummaryDescriptionValue Range
SSession statusOn as long as the session is active.0/1
FanFanOutput for fan control.0/1
APIAPI ConnectorIntelligent API based connector.
API Commands
-




Parameters

AbbreviationSummaryDescriptionUnitValue RangeDefault Value
RemRemanence inputRemanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
-0/10
FsdFan start delayDelay before the fan is switched on after the session started.s0...∞30
FPetFan / Movement extend time1. Time starts with the falling edge of output (S) and extends output (Fan) by set time.
2. When using input (P), time starts with the falling edge of input (P) and extends outputs (S) and (Fan) by set time.
s0...∞180