PV Production Forecast

The PV Production Forecast function block predicts photovoltaic production without requiring physical metering or orientation data. It uses absolute irradiance (GHI) forecast data from the Weather Service to generate predictions of photovoltaic production. Please note, it does not account for potential inverter limitations.

An active Weather Service is required to use this block.

Table of Contents


Inputs

Abbreviation Summary Description Value Range
Off Off input Sets the Ready output to OFF and the prediction outputs to -1 0/1




Outputs

Abbreviation Summary Description Unit Value Range
Ppwr Potential Power Indicates the PV power output that could currently be generated based on solar radiation provided by the weather service. -1 if no prediction can be provided. kW
Pp Predicted period Outputs the prediction for the given period of time starting from the next full hour. -1 if no prediction can be provided. kWh
Ptd Predicted today Outputs the prediction for today. -1 if no prediction can be provided. kWh
Pnd Predicted next day Outputs the prediction for the next day. -1 if no prediction can be provided. kWh
Ready Prediction provided OFF if control is locked via Off input or if no prediction can be provided (loss of internet connection, subscription expired, etc) - 0/1
API API Connector Intelligent API based connector.
API Commands
- -




Parameters

Abbreviation Summary Description Unit Value Range Default Value
Period Calculated Period Forecast is calculated over this period of time starting from the next full hour. h 0...72 24




Properties

Summary Description Value Range Default Value
Max PV power [kWp] PV's theoretical maximum power production 0...∞ 0




Calculation

The PV production forecast is calculated based on the ratio between the current GHI (Absolute Radiations) forecast and the theoretical maximum GHI. This value is then multiplied by the maximum installed PV power (kWp) to determine the estimated PV production.

Formula:
(GHI from Weather Service / theoretical GHI max) * installed kWp = estimated PV production

Example:

  • GHI (absolute radiations) from Weather Service: 486.94 W/m²

  • Theoretical GHI max (standardized value): 1361 W/m²

  • Installed PV system size (kWp): 10 kWp

  • Calculation: (486.94 / 1361) * 10 = 3.6 kWh