The Loxone Fan Control Tree is an AC ceiling fan controller utilizing series capacitors to adjust the speed in four discrete steps.
Datasheet Fan Control Tree 230 V
Datasheet Fan Control Tree 120 V
Table of Contents
Mounting↑
The Fan Control Tree is installed on a DIN rail in a suitable enclosure.
Connect the power supply, the Tree interface, and the ceiling fan. The output is designed to control a single ceiling fan with a load between 30 W and 120 W. It supports four speed levels (Off), Slow, Medium, Fast, and Maximum. The availability and performance of these speed levels may vary depending on the connected fan's load within the supported range.
Commissioning↑
After establishing the power supply, the device starts, and the status LED blinks orange shortly after a successful connection to the Miniserver via the Tree Interface.
Then follow the pairing procedure on the Tree Interface.
Programming↑
The Loxone Fan Control Tree is programmed and set up using the Step Selector function block in Loxone Config.
Actuators↑
Summary | Description | Unit |
---|---|---|
Mode | Off, Low, Medium, High, Maximum | - |
API Connector | Text |
Diagnostic Inputs↑
Summary | Description | Unit | Value Range |
---|---|---|---|
Online Status Fan Control Tree | Indicates whether the device can be reached by the Miniserver. Diagnostics for Air devices Diagnostics for Tree devices Diagnostics for Extensions |
Digital | 0/1 |
System temperature | Provides the internal device temperature. This is often the temperature of the CPU or another location in the device. |
° | ∞ |
Temperature Shutdown | Input is active, when the outputs of the device have been switched off due to high device temperature. Possible reasons: Ambient temperature too high, outputs overloaded. | Digital | 0/1 |
Properties↑
Summary | Description | Default Value |
---|---|---|
Monitor online status | If checked, you will be notified via System Status or the Mailer if the device is no longer available or goes offline. | - |
Serial number | Specifies the serial number of the device. Enter 'Auto' to automatically pair a Tree device with unknown serial number. This can only be used if there is only one Tree device of the same type. Save in the Miniserver to pair the Tree device. Afterwards the program must be loaded from the Miniserver to transfer the actual serial number of the Tree device into the program. |
- |
Switch off status LEDs | If checked, the status LEDs on the device are switched off in normal operation. In the event of a fault, the device will continue to alert you to its status LEDs. |
- |
Safety Instructions↑
The installation must be carried out by a qualified technician in accordance with all applicable regulations.
This device must be installed on a DIN rail within a standard electrical distribution enclosure and may only be installed by qualified personnel.
To ensure protection against electrical contact and fire hazards, the final installation must include a housing that complies with applicable safety standards and approvals.
For installations in the US and Canada, this device must be installed in a metal enclosure or one rated 5VA or higher.
To power the unit on or off during installation or in the event of a failure, a disconnecting device must be provided. This device must be clearly visible and easily accessible.
Using the unit in a manner not specified by the manufacturer may impair the product’s built-in safety features.
This device requires no maintenance and should only be cleaned using a dry cloth.
Documents↑
Datasheet Fan Control Tree 230 V
Datasheet Fan Control Tree 120 V