The Relay Extension features 14 dry contact relay outputs.
Table of Contents
Commissioning↑
The Relay Extension is installed on a DIN rail in a suitable enclosure.
Connect the power supply and Link communication to the Miniserver.
Connect the loads to the relay terminals. For loads exceeding 12A, use a wire cross-section of 2.5mm².
![]() |
For thermal reasons the total load rating must not exceed 48A (IEC) or 45A (UL). |
The Extension starts after switching on the power supply, and the status LED will flash orange after a short time when the connection to the Miniserver is established.
Then follow the pairing procedure
Wiring examples↑
Actuators↑
Summary | Unit | Value Range |
---|---|---|
Actuator (Relay) 1 | Digital | 0/1 |
Actuator (Relay) 2 | Digital | 0/1 |
Actuator (Relay) 3 | Digital | 0/1 |
Actuator (Relay) 4 | Digital | 0/1 |
Actuator (Relay) 5 | Digital | 0/1 |
Actuator (Relay) 6 | Digital | 0/1 |
Actuator (Relay) 7 | Digital | 0/1 |
Actuator (Relay) 8 | Digital | 0/1 |
Actuator (Relay) 9 | Digital | 0/1 |
Actuator (Relay) 10 | Digital | 0/1 |
Actuator (Relay) 11 | Digital | 0/1 |
Actuator (Relay) 12 | Digital | 0/1 |
Actuator (Relay) 13 | Digital | 0/1 |
Actuator (Relay) 14 | Digital | 0/1 |
Diagnostic Inputs↑
Summary | Description | Unit | Value Range |
---|---|---|---|
Online Status Relay Extension | Digital | 0/1 | |
System temperature | ° | ∞ | |
Temperature Shutdown | If the CPU temperature reaches a critical point, the outputs of the device are switched off. This can be due to short-circuits, overloaded switching loads or too high an ambient temperature. | Digital | 0/1 |
Properties↑
Summary | Description | Default Value |
---|---|---|
Serial Number | Specifies the serial number of the device. For Extensions: Enter 'Auto' to automatically pair an extension with unknown serial number. This can only be used if there is only one Extension of the same type. Save into the Miniserver, in order to pair the Extension. Afterwards the program must be loaded from the Miniserver to transfer the actual serial number of the Extension into the program. |
- |
Monitor Online Status | When selected, you will be notified via System Status or the Mailer if the device is no longer available or goes offline. | - |
Safety Instructions↑
The installation must be carried out by a qualified technician in accordance with all applicable regulations.
The installation requires a suitable enclosure to ensure protection against contact, water and dust.
The device must not be used as part of safety-critical systems.