TECHNICAL SPECIFICATIONS

  • Power supply: 24 VDC
  • Power consumption: 115mW ~
  • Temperature & humidity measurement *
  • 5 touch points
  • Optional click feedback when touched
  • Status LED
  • Temperature measuring range: -20 … + 80 ° C
  • Temperature tolerance: +/- 0.5 ° C
  • Measuring range Humidity: 0 – 100%
  • Moisture tolerance: +/- 2% RH
  • Ambient temperature: 0 … + 55 ° C
  • Dimensions: 55mm x 55mm without frame
  • Cable diameter 0.25-0.8 mm²
  • Stripped cable length: 5mm
  • Protection: IP20

Icon Exclamation Mark LoxonePlease note temperature and humidity is sensed through the touch trees closed housing which can mean a delay in sensing time. For the rapid detection of changes in the ambient humidity (eg. For ventilation control in the bathroom), we recommend a sensor with an open housing design as the Loxone Temperature & Humidity Sensor Air.

MOUNTING SUGGESTIONS

When mounting the Touch Tree and Touch Pure Tree we suggest that you specify the mainland European style circular back boxes for the neatest finish. Such boxes are designed to be more slimline than the standard UK metal and plastic dry lining boxes. The can be sourced from such places as RS Components.

European Style Circular Backbox

SETUP

To connect the Touch tree connect the 24V power (orange/Orange-white terminals) and the Tree terminals (Green/Green-white terminals). The device will flash orange when connected.

Loxone Touch Tree COnnectors

For full Loxone Config setup instructions click here.

TOUCH POINTS

The touch points may be used in Loxone Config as digital inputs. Every touch point is a digital input.

For Press and Hold, you will need to set the ‘Receive Timeout’ properties of the Digital Input to 0.

en_kb_product_touch_air_points

COMBINED KEY T5

The T5 output combines all 5 of the digital outputs of the Touch tree. This is designed to speed up the programming of the Loxone standard.
The following functions are supported here:

  • Automatic blinds: inputs Cu (touch point 1) and Cd (touch point 4)
  • Light Control: Scene + (touch point 3)
  • Music Server Zone: inputs V + (touch point 2) and V- (touch point 5)
  • Central block control (double/triple click of centre key)

Connect the T5 output to the T5 input of the desired blocks.
In order to program and user-defined functions, ensure check boxes for inputs are activate in properties.