Window

Controls a window.

Table of Contents


Inputs

Abbreviation Summary Description Unit Value Range
Co Complete open - 0/1
Cc Complete close - 0/1
Pos Position of window Move window to specified position. % 0...100
Po Partial open with push & hold - 0/1
Pc Partial close with push & hold - 0/1
Wp Weather protection Window is closed and locked for further operation when on.
Control via user interface is still possible.
- 0/1
Off Off Pulse stops movement. On locks the block.
Dominating input.
- 0/1
Io Is open Input is used to report the “fully opened” position via a limit switch or similar. - 0/1
Ic Is closed Input is used to report the “fully closed” position via a limit switch or similar. - 0/1




Outputs

Abbreviation Summary Description Value Range
Op Open 0/1
Cl Close 0/1
Pos Position of Window Position of the window (0.0 = open, 1.0 = closed) 0...1
AC API Connector Intelligent API based connector. -




Parameters

Abbreviation Summary Description Unit Value Range Default Value
Rem Remanence input Remanence input: If active, the function block retains its previous state after a Miniserver reboot. - 0/1 0
Opd Opening duration s 0...∞ 5
Cld Closing duration s 0...∞ 5
minTd Minimum travel time Minimum travel time at pulse on input (Po) or (Pc). s 0...∞ 0,4
Mld Motor lock duration Duration of motor lock between direction changes s 0...∞ 0,5