Window

Controls a window.

Table of Contents


Inputs

Abbreviation Summary Description Unit Value Range
Co Complete open If in motion, stops. - 0/1
Cc Complete close If in motion, stops. - 0/1
Tg Toggle Toggles between open, stop, close.
For single button control.
- 0/1
Pos Position of window Move window to specified position. % 0...100
Po Partial open with push & hold - 0/1
Pc Partial close with push & hold - 0/1
Wp Weather protection Window is closed and locked for further operation when on.
Control via user interface is still possible.
- 0/1
Off Off Pulse stops movement. On locks the block.
Dominating input.
The name of the connected sensor is used in the user interface.
- 0/1
Io Is open Input is used to report the “fully opened” position via a limit switch or similar. - 0/1
Ic Is closed Input is used to report the “fully closed” position via a limit switch or similar. - 0/1
CPos Current position Input indicating the current tilt position or opening width of the window. % 0...100




Outputs

Abbreviation Summary Description Unit Value Range
Op Open - 0/1
Cl Close - 0/1
Pos Position of Window Position of the window (0.0 = closed, 1.0 = open) - 0...1
TPos Target position Output for target tilt position or target opening width (Schüco).
- When input (Po) is ON (rising edge), the target position is set to 100.
- When input (Pc) is ON (rising edge), the target position is set to 0.
- If either input (Po) or input (Pc) are OFF (falling edge), the target position adopts the value of input (CPos). If input (CPos) is not connected, the target position will be calculated.
% 0...100
AC API Connector Intelligent API based connector.
API Commands
- -




Parameters

Abbreviation Summary Description Unit Value Range Default Value
Opd Opening duration s 0...∞ 5
Cld Closing duration s 0...∞ 5
minTd Minimum travel time Minimum travel time at pulse on input (Po) or (Pc). s 0...∞ 0,4
Mld Motor lock duration Duration of motor lock between direction changes s 0...∞ 0,5