Controls a window.
Table of Contents
Inputs↑
Abbreviation | Summary | Description | Unit | Value Range |
---|---|---|---|---|
Co | Complete open | If in motion, stops. | - | 0/1 |
Cc | Complete close | If in motion, stops. | - | 0/1 |
Tg | Toggle | Toggles between open, stop, close. For single button control. |
- | 0/1 |
Pos | Position of window | Move window to specified position. | % | 0...100 |
Po | Partial open with push & hold | - | 0/1 | |
Pc | Partial close with push & hold | - | 0/1 | |
Wp | Weather protection | Window is closed and locked for further operation when on. Control via user interface is still possible. |
- | 0/1 |
Off | Off | Pulse stops movement. On locks the block. Dominating input. The name of the connected sensor is used in the user interface. |
- | 0/1 |
Io | Is open | Input is used to report the “fully opened” position via a limit switch or similar. | - | 0/1 |
Ic | Is closed | Input is used to report the “fully closed” position via a limit switch or similar. | - | 0/1 |
Outputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
Op | Open | 0/1 | |
Cl | Close | 0/1 | |
Pos | Position of Window | Position of the window (0.0 = closed, 1.0 = open) | 0...1 |
AC | API Connector | Intelligent API based connector. API Commands |
- |
Parameters↑
Abbreviation | Summary | Description | Unit | Value Range | Default Value |
---|---|---|---|---|---|
Rem | Remanence input | Remanence input: If active, the function block retains its previous state after a Miniserver reboot. The state of the function block is saved: – When saving to the Miniserver – At a planned reboot – Before a backup – Once per hour The data is saved on the SD card. |
- | 0/1 | 0 |
Opd | Opening duration | s | 0...∞ | 5 | |
Cld | Closing duration | s | 0...∞ | 5 | |
minTd | Minimum travel time | Minimum travel time at pulse on input (Po) or (Pc). | s | 0...∞ | 0,4 |
Mld | Motor lock duration | Duration of motor lock between direction changes | s | 0...∞ | 0,5 |