Radio Buttons

Up to 8 radio buttons, only one output can be active at a time. E.g. pulse at input (I3) activates output (O3).

Table of Contents


Inputs↑

Abbreviation Summary Description Value Range
I1-8 Input 1-8 Switches the respective output 1-8 On 0/1
+ Next output 0/1
- Previous output 0/1
Sel Select output Switches to specific output. ∞
Off Off Pulse: Outputs are reset / switched off.
On: Block is locked.
Dominating input.
The name of the connected sensor is used in the user interface.
0/1
DisPc Disable periphery control Disables all inputs when On. (e.g Child lock, cleaning)
Control via user interface is still possible.
0/1




Outputs↑

Abbreviation Summary Description Value Range
O1-8 Output 1-8 0/1
N Number of active output ∞
AC API Connector Intelligent API based connector.
API Commands
-




Parameters↑

Abbreviation Summary Description Value Range Default Value
Rem Remanence input Remanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
0/1 0
Max Max. outputs Maximum number of used outputs when using +/- inputs. ∞ 8
Sk0 Skip 0 'All-off' (0) is skipped when switching with +/- when On.
Applies only to object inputs, not to the buttons in the user interface.
0/1 0




Properties↑

Summary Description Default Value
Edit outputs Edit output names -