Pulse Meter Bidirectional

This bidirectional meter is suitable for recording consumption and delivery of various utilities such as electricity, gas, water, heat, etc.

For this purpose, the pulses of a physical meter with pulse output (S0) are read.

Together with other meter function blocks, various consumers, producers or storage units in the building can be linked via the Energy Flow Monitor for an overall display.

Table of Contents


Inputs

Abbreviation Summary Description Value Range
Pc Pulse consumption For meters with pulse output (S0), connected to digital inputs. 0/1
Pd Pulse delivery For meters with pulse output (S0), connected to digital inputs. 0/1
Fc Frequency consumption For meters with pulse output (S0), connected to digital inputs used as frequency counter. 0...∞
Fd Frequency delivery For meters with pulse output (S0), connected to digital inputs used as frequency counter. 0...∞
R Reset Pulse: Meter reading outputs are reset.
On: Block is locked.
0/1




Outputs

Abbreviation Summary Description Value Range
Pf Power or flow Current power/flow calculated using inputs (Pc) and (Fc) is output as a positive value.
Current power/flow calculated using inputs (Pd) and (Fd) is output as a negative value.
Mrc Meter Reading consumption 0...∞
Rdc Reading today consumption 0...∞
Rldc Reading yesterday consumption 0...∞
Rmc Reading this month consumption 0...∞
Rlmc Reading last month consumption 0...∞
Ryc Reading this year consumption 0...∞
Rlyc Reading last year consumption 0...∞
Mrd Meter Reading delivery 0...∞
Rdd Reading today delivery 0...∞
Rldd Reading yesterday delivery 0...∞
Rmd Reading this month delivery 0...∞
Rlmd Reading last month delivery 0...∞
Ryd Reading this year delivery 0...∞
Rlyd Reading last year delivery 0...∞
AC API Connector Intelligent API based connector.
API Commands
-




Parameters

Abbreviation Summary Description Value Range Default Value
Npc Number of pulses per unit 0...∞ 1000
Npd Number of pulses per unit 0...∞ 1000
Mroc Meter reading offset consumption Value is added to output (Mrc). 0
Mrod Meter reading offset delivery Value is added to output (Mrd). 0




Properties

Summary Description Default Value
Report invalid Meter Reading When selected, you will be notified if invalid Meter Reading values have been detected. For instance, when a physical counter sends unrealistic values due to transmission errors. -




Meter reading and units

The physical meter provides a certain number of pulses per unit of quantity, this must be set at parameter (Np). The block uses this to form the meter reading (Mr), calculates the power or flow rate (Pf), and records the statistics.

The units for Pf/Mr must be hour-related and must match in magnitude so that Pf is calculated correctly.
Examples:
Pf=kW, Mr=kWh
Pf=W, Mr=Wh
Pf=l/h, Mr=l
Pf=m³/h, Mr=m³
Pf=kg/h, Mr=kg