Belimo Air

Belimo is one of the leading manufacturers in the area of climate control.
The Loxone Belimo Air is an interface to integrate up to 16 Belimo MP-Bus devices. With the native MP-Bus integration, Belimo products become a native member of Loxone Config and the Miniserver.

Datasheet Belimo Air

Table of Contents


Mounting↑

Install the device in a suitable installation box.

Connect the power supply (orange/white terminal).

Connect the orange MP-Bus lead to the MP-Bus nodes. The GND of the MP-Bus nodes must be connected to the GND of the Belimo Air.

While 24VAC power supply is possible for many MP-Bus devices, the Belimo Air can only be supplied with 24VDC.


Commissioning↑

Der Lernmodus ist im Auslieferungszustand nach Anschließen der Stromversorgung aktiv. Dies wird durch Rot/Grün/Orange wechselndes Leuchten der Status LED angezeigt.

Then follow the pairing procedure

To activate the pairing mode manually, switch off the power for 10 seconds, then switch it back on. If no connection to a Miniserver can be established for two minutes, then pairing mode is activated for 30 minutes.


Commissioning Belimo devices↑

There are 3 ways to insert Belimo devices:

If Belimo devices are addressed via the Belimo App, their address and serial number is entered in the properties:

For more informations, please visit the Belimo Documentation.


Diagnostic Inputs↑

Summary Unit Value Range
Online Status Belimo Air Digital 0/1




Properties↑

Summary Description Value Range Default Value
Monitor Online Status When selected, you will be notified via System Status or the Mailer if the device is no longer available or goes offline. - -
Serial Number Serial number of the Air device - -
Device type Air device type - -
MP-Bus Supply Specifies if MP-Bus supply is active - -
Device Status Update Cycle[s] Belimo device specific status update cycle time in seconds (10 - 600) 10...600 10




Documents↑

Datasheet Belimo Air




Inputs, outputs, status values and error messages