This function block will output a pulse with an adjustable duration when a rising edge is seen on the input of the block.

Loxone Musterkoffer


After a rising edge at the input Tr the output is enabled. If the input at Tr is active longer than the duration of the output pulse (defined with parameter T) then there will be no effect on the state of Q. The output pulse is restarted with every rising edge at Tr.

If the input R is activated, the timer is reset and the output Q is disabled. Then only after a new rising edge at the input Tr, will the timer be restarted.

The block can be set to be retentive, this is done by clicking on the battery symbol to set the red NOT dot on the block (input is by default inactive).




 Inputs  Tr Trigger  
   R Reset  0/Off
 Outputs  Q Output  
 Parameters  tl_files/loxone/documentation/EN-UK/function_blocks/lighting_controller/Untitled.png Remanence   0/Off
   T Duration of output pulse [s]  2