Roof Window Shading

Controls the shading for a roof window.

Table of Contents


Inputs

AbbreviationSummaryDescriptionUnitValue Range
TgToggleToggles between open, stop, close.
For single button control.
-0/1
PoPartial open with push & hold-0/1
PcPartial close with push & hold-0/1
CoComplete openIf in motion, stops.-0/1
CcComplete closeIf in motion, stops.-0/1
DwcDoor/window contactOpens shading completely and locks the block when On.
Manual operation via user interface is still possible.
(0 = closed, 1 = open).
-0/1
WaWind alarmMoves shading to the wind alarm position set in parameter (Wap) and locks the block(can still be operated through the App/Webinterface). Used for storm protection. Active Automatic is only suspended instead of cancelled. After Wa end, automatic is restarted with a positive edge on Sps or of the sunshine-systemvariable. Automatic conditions are not re-evaluated on end on windalarm. If both conditions are permanently active during windalarm, automatic can be restarted via pulse on Spr.
The name of the connected sensor is used in the user interface.
-0/1
OffOffPulse stops movement. On locks the block.
Dominating input.
The name of the connected sensor is used in the user interface.
-0/1
PosPosition of shadingMove the shading to the specified position.%0...100
T5T5 controlButton 1: Complete open
Button 4: Complete close
-
DisPcDisable periphery controlDisables inputs Tg, Po, Pc, Co, Cc, So, T5 when On. (e.g Child lock, cleaning)
Control via user interface is still possible.
-0/1
SoSlightly openVenetian blinds close completely and move slats in horizontal position according to parameter (Rd).
Roller blinds, curtains and awnings move into position according to parameter (Rd).
-0/1
SpsSun position automatic startActivates the sun position automatic when On at the beginning of the shading period, or also with a pulse during the shading period.
The sun position automatic is deactivated for the rest of the day, if block is operated manually. Pulse on (Spr) followed by a rising edge on (Sps) or pulse on (Spr) while (Sps) is active, restarts the sun position automatic.
-0/1
DisSpDisable sun position automaticDisables the sun position automatic when On.-0/1
SprSun position automatic restartPulse followed by a rising edge at input (Sps) or pulse while input (Sps) is active, restarts the sun position automatic.-0/1




Outputs

AbbreviationSummaryDescriptionValue Range
OpOpen
This output is only visible in certain configurations.
0/1
ClClose
This output is only visible in certain configurations.
0/1
PosPosition of shadingPosition of the shading (0.0 = open, 1.0 = closed)0...1
WdsWind, door/window contact stateOn when Input (Wa) of the block or of a linked central block is active or when input (Dwc) is active.0/1
OffOffActive when input (Off) is 1.0/1
SpSun position automaticOn, if input (Sps) = 1 and input (DisSp) = 0 ...and if the setting “Use sunshine variable” is checked and the sun is shining,
or if the Automation based on sun position is switched on in the App.
0/1
APIAPI ConnectorIntelligent API based connector.
API Commands
-




Parameters

AbbreviationSummaryDescriptionUnitValue RangeDefault Value
WapWind alarm position0 = Completely open
1 = Completely closed
-0/10
OpdOpening durations0...∞75
CldClosing durations0...∞75
MldMotor lock durationDuration of motor lock between direction changes.s0...∞0,5
TdcTime double-clickDouble click duration on inputs (Po), (Pc) for complete open / close.
0 = Not used
s0...∞0,3
TlcTime long-clickLong-click duration on inputs (Po), (Pc) for complete open / close.
If you prefer a double-click, then set the value > (Opd) or (Cld).
0 = Always start complete travel.
s0...∞3
minTdMinimum travel durationMinimum travel time at pulse on input (Po) or (Pc).s0...∞0,4
SpmSun position automatic mode0 = Automatic stays Off if shading is closed. If the input (Sps) is active, a pulse on (Spr) restarts the sun position automatic.
1 = Automatic always allowed.
-0...11
SpeSun position automatic end action0 = No action
1 = Complete open
2 = Complete close
-0...21
DirCompass directionCompass direction of the window:
0 = north
90 = east
180 = south
270 = west
-1 = not configured
°-1...359-1
DtsDirection tolerance startDirection tolerance for the sun position automatic when the sun enters the shading area.°0...9085
DteDirection tolerance endDirection tolerance for the sun position automatic when the sun exits the shading area.°0...9085
PiPitchRoof or window pitch.
0 = horizontal
90 = vertical
°0...9030
SposSun position automatic start offsetStart offset of the sun position automatic relative to Sunrise.min-90...9030
SpoeSun position automatic end offsetEnd offset of the sun position automatic relative to Sunset.min-90...90-30
SopSlightly open positionPosition used for input (So) and (Sps).%0...10080




Properties

SummaryDescriptionValue RangeDefault Value
Use sunshine variableSun position automatic is only activated if the system variable Sunshine and the input Sps are active.--
Number of activity entriesNumber of entries in the activity log.
0: log is disabled
The activity log tracks relevant changes since program start.
0...10020



Direction parameters

Dir: Compass direction of the shading device relative to the geographical north. (0 = North, 90 = east, 180 = south, 270 = West)

Dts: Direction tolerance when the sun enters the shading device. The directional tolerance is relative to the perpendicular angle of the shading device. Consider, for example, building protrusions. If your shading device is not affected, you can leave this at its default value of 85º.

Dte: Direction tolerance when the sun exits the shading device. The directional tolerance is relative to the perpendicular angle of the shading device. Consider, for example, building protrusions. If your shading device is not affected, you can leave this at its default value of 85º.


Start / End offsets

With parameter (Spos), the sun position automatic will be delayed by this number of minutes after sunrise.
This is relevant for windows that may not get the sun directly after sunrise.

With parameter (Spoe), the sun position automatic will be brought forward by this number of minutes before sunset.
This is relevant for windows that may be affected by the sun prior to sunset.

There are two possible applications for the two parameters:

Often the sun is obscured by other buildings, structures or trees after sunrise and before sunset. Here, the start or end time of the sun position automatic can be adapted to accommodate for these.

Another possibility is to shift the times so that sunrise or sunset can be seen with the shading open.


Enable Sun Position Automatic via User Interface

The sun position automatic can be started manually via the user interface, thereby blinds are lowered when the sun is at the window. Whether the sun is shining, it is cloudy, or the Sps input of the block is active or not is not taken into account.


Timing Diagram


History

In the user interface, the history of the function block can be displayed.
A maximum of 100 entries can be shown.
When you restart or save to the Miniserver, the history is cleared.