Push Button

On/Off push-button

Table of Contents


Inputs

AbbreviationSummaryDescriptionValue Range
TrTriggerSwitches output (O) on for the duration set in parameter (Don).
Another pulse extends the on-duration.
0/1
OffOffPulse: Outputs are reset / switched off.
On: Block is locked.
Dominating input.
The name of the connected sensor is used in the user interface.
0/1
DisPcDisable periphery controlDisables inputs (Tr), (Off) when On. (e.g Child lock, cleaning)
Control via user interface is still possible.
0/1




Outputs

AbbreviationSummaryDescriptionValue Range
OOutputOn for the duration set in parameter (Don).0/1
APIAPI ConnectorIntelligent API based connector.
API Commands
-




Parameters

AbbreviationSummaryDescriptionUnitValue RangeDefault Value
RemRemanence inputRemanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
-0/10
DonOn-duration of output (O)0 = Output (O) remains active as long as the button is pressed.s0...∞0,3



Timing Diagram