Hotel Lighting Controller

Hotel lighting controller for dimming, switching and RGB lighting

Table of Contents


Inputs

AbbreviationSummaryDescriptionValue Range
I1-20Trigger input 1-20 for dimmer / switching input for digital circuits0/1
S10Trigger selection scene 10Trigger selection lighting scene 100/1
S11Trigger seletion scene 11Trigger selection lighting scene 110/1
S12Trigger seletion scene 12Trigger selection lighting scene 120/1
S13Trigger seletion scene 13Trigger selection lighting scene 130/1
RResetReset input of the hotel lighting controller0/1
ICCard switch0/1
ISService buttonInput service button
Depending on service mode
0/1
AIrRoom stateStatus input
0 = 'Not booked'
1 = 'Booked'
2 = 'Guest checked in'
IDDoor contactInput door contact0/1
DisMoDisable motion sensor inputDisable input of the motion sensor0/1
MoMotion sensorMotion sensor input0/1
DisDisableDisable-input of the hotel lighting controller0/1




Outputs

AbbreviationDescriptionValue Range
AQ1-20Analog output of actuator/dimmer 1-20
on RGB - %-value red + %-value green * 1000 + %-value blue * 1000000
AQsAnalog output currently active scene
QPPresence Output0/1
QSService Output0/1
QDService completed output0/1
AQrmAnalog output for room service status
1 = Vacant/not cleaned
2 = Occupied/not cleaned
3 = Vacant/cleaned
4 = Occupied/cleaned




Parameters

AbbreviationSummaryDescriptionUnitValue RangeDefault Value
RemRemanence inputRemanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
-0/10
MSService staff modeInput parameter - Service Staff mode
0 = Long click service button after inserting card
1 = Service button signal before inserting card
2 = Service button On before inserting card
3 = Card has to be inserted twice
-2
TMDuration of Service Staff modeParameter - Duration for Service Staff modes60
ToDuration press and hold for 'All off'Parameter input duration long click for 'All off's2
TlTimeout for leaving roomInput parameter - Timeout for leaving the room
Enter 0 if no automatic off after leaving is to be triggered
s60
MMax time between pulsesParameter - Maximum duration between 2 pulsess0,35
SIStepParameter - Step size for dimmer in %%2
STStep rateParameter - Step rate for dimmers0,2
MinMinimum valueParameter input minimum dimmer value (0 to 50%)%15
MaxMaximum valueParameter input maximum dimmer value (50 to 100%)%100
LDo not set last valueParameter - do not set last dimmer value (OFF = short click sets last value when switched off)-0/10
THDuration OnInput parameter - Duration ON for motion sensor
Countdown starts from falling edge of Mo
s180




Properties

SummaryDescriptionDefault Value
Lighting scenesLighting scene management-



Presence Simulation

This function block has a presence simulation.
Activate and define the presence simulation in the properties window: