Extension

TECHNICAL DATA

  • 12x digital inputs 24VDC (also suitable for use as frequency inputs e.g. In combination with a wind sensor)
    • Minimum pulse width: 3ms
    • Maximum frequency: 150Hz
    • Accuracy: +/- 1Hz
    • Input resistance: 10kΩ
  • The 24VDC supply on the digital inputs is rated at 100mA, it is not intended for high loads.
  • 4x analogue inputs
    • 0 – 10VDC with 10 bit resolution
    • Can also be used as digital inputs (up to 24VDC): < 1V equivalent to logic 0, i.e. Off ; 1 – 10V equivalent to logic 1, i.e. On)
    • Input resistance: 10kΩ
  • 8x digital outputs (relays) 250VAC 5A at cosφ=1, 30VDC 5A
    • (for large loads use a coupling relay)
  • 4x analogue outputs 0 – 10VDC
    • Maximum 20mA output load
  • Compact design for DIN rail mounting
  • Dimensions: 156 x 88 x 57mm (T9 housing)
  • Power consumption without relays: 60mA
  • Power consumption with all relays: 120mA
  • Power supply via 24VDC adapter
  • Protected against excessive voltage at the relay
  • Protection: IP20
  • Operating Temperature: 0 to 50°C
  • Connected via Loxone Link
  • Safety shutdown: If the CPU temperature increases over 87°C, all the digital outputs are turned off. Once the temperature drops below 72°C, the respective digital outputs are turned on. The CPU temperature is updated on startup and if there is a temperature change of more than 5°C.

DIMENSIONS

Dimmer Extension Loxone Dimensions

INSTALLATION

  • Mount the Extension on the DIN rail
  • Connect 24VDC power supply, but do not switch on until the whole installation is completed
    (we recommend looping power through the Miniserver)
  • Connect the inputs and outputs
  • Connect the Loxone Link
  • Note: If this is the last extension, terminate the Loxone Link with a 120Ω resistor (included with the Miniserver)
  • Turn on the power supply
  • After a few seconds, the left LED will flash green if the Extension is already configured, orange if not.

CONFIGURING EXTENSIONS

Click here to find out how

FIND OUT MORE

Contact Us

DOWNLOADS

Extension Quick Connection Guide (pdf)

Extension User Manual (pdf)

Download a datasheet for the Extension’s relays (pdf)

IEC CB Test Certificate (pdf)

NRTL Certificate (pdf)

Extension EG Declaration of Conformity (pdf)

RoHS Declaration of Conformity (pdf)