Contrôleur de sauna avec évaporateur

Loxone Musterkoffer

Fonctions

The Sauna controller with evaporator block allows you to control and monitor your sauna. All conventional heaters are compatible (switched heating and 0-10V proportional). The evaporator can be switched on and off but can also be controlled with an analogue 0-10V signal.

The module has a timer function, fan and drying control, as well as a safety shut down.

You can choose between different operating modes such as steam sauna, Finnish sauna, herbal sauna etc.

The block can also be used in the user interface, for control whilst on the move!

Make sure to select appropriate sensors for the heat in the sauna!
See here our sauna temperature sensor in the webshop.

Außerdem kann der Baustein Saunasteuerung über die Visualisierung und somit auch von unterwegs bedient werden. Beachten Sie dabei die Sicherheitsvorschriften und Gesetzesbestimmungen des jeweiligen Landes. Ebenso wäre ein Türkontakt empfehlenswert, um auch von unterwegs zu wissen, ob die Tür geschlossen ist.

En outre, une protection thermique de surchauffe doit être installé!

Configuration basique

Connect the temperature sensor for the sauna to the input AI, and then conect the humidity sensor to AIh.

The outputs are for the various types of heaters, AQ for 0-10V analogue, Q1, Q2 and Q3 for stage L1, L2 and L3 heaters. If the heater is a single phase using Q1 we need to set the parameter M to 1. 

Where you connect the evaporator to depends on the control type. If it is 0-10V analogue then connect to AQv, if it is digital on/off then connect to Qv. 

Finally connect the fan to the output Qf. 

Contrôleur de sauna avec évaporateur - Loxone

You can now control the block in the user interface. The sauna on/off function (Tr input) can also be done through a switch on the wall, for example outside the sauna itself.

When the block is in a manual mode the target values for temperature (input T) and humidity (input H) are used.

If the evaporator has a water shortage sensor this can be connected to the input LW so an alert can be triggered. Also if the input LW is triggered and has a value of 1 (digital input) the evaporator will no longer turn on.

Vue d'ensemble

INPUTS

DESCRIPTION

 
AIm

Analogue input for mode

0 = Off
1 = Manual Finnish sauna
2 = Manual humidity sauna
3 = Automatic Finnish sauna
4 = Automatic herbal sauna
5 = Automatic hot bath sauna
6 = Automatic steam sauna

IFm

Digital input

Manual Finnish sauna
IHm

Digital input

Manual humidity sauna
IF

Digital input

Automatic Finnish sauna
IH1

Digital input

Automatic herbal sauna
IH2

Digital input

Automatic hot bath sauna
IH3

Digital input

Automatic steam sauna
Tr

Trigger digital input

Turns the sauna on or off
T

Analogue input for desired target temperature in manual mode

Set either with a virtual input connector or a timer switch

AI

Analogue input For actual temperature, connect the sauna sensor to this

H

Analogue input for desired target humidity in manual mode Set either with a virtual input connector or a timer switch

AIh

Analogue input For actual humidity, connect the sauna humidity sensor to this

Tf

Trigger digital input for the fan   Turns the fan on and off, output Qf

Tc

Starts the hourglass timer The output AQt shows the time counting down and Qta gives the timer's status, can set the time with parameter T, Qte pulses when the timer is finished

D

Türkontakt Eingang für Türkontakt (dient nur zur Anzeige in der Visualisierung)

Ab

Analogue input For the bench temperature sensor

P

Digital input Used for presence detector 

LW

Digital input  Gives the status of water shortage

R

Reset Sets all the outputs to off

Dis

Disable Disables all the inputs and is useful for childlock function

OUTPUTS

DESCRIPTION

 
AQ

Analogue output

0-10V control
Q1

Digital output

For turning Phase 1 (L1) on/off
Q2

Digital output

For turning Phase 2 (L2) on/off
Q3

Digital output

For turning Phase 3 (L3) on/off
AQv

Analogue output

For controlling the evaporator with 0-10V
Qv

Digital output

For controlling the evaporator digitally
Qa

Status output for whether the sauna is active or not

On when the sauna is active
Qf

Digital output for fan control

Switched on by input Tf
AQt

Remaining time for hourglass timer

Time is in seconds [s]
Qd

Digital output status for airing phase

On when the airing phase is active
AQm

Current operating mode

0 = Off
1 = Manual Finnish sauna
2 = Manual humidity sauna
3 = Automatic Finnish sauna
4 = Automatic herbal sauna
5 = Automatic hot bath sauna
6 = Automatic steam sauna

Qe

Error status

Pulses when actual temperature is higher than desired temperature, see parameter Ts

AQs

Status output for target temperature

Displays the current target temperature

AQh

Status output for target humidity

Displays the current target humidity
Qte

Status output for end of timer

Pulse when timer countdown finishes

Qta

Digital output Gives the timer's status (on/off)

PARAMETER 

DESCRIPTION

 
Tc

Temperature correction

Adjustment for the actual temperature in the seating position (use if no bench sensor present)
Td

Airing temperature 

Temperature required for the airing period
Tn

Fan duration after airing time finished

Running time of the fan required to achieve Td
Tt

Duration of hourglass timer

This begins with each new pulse on input Tc. The remaining time is displayed on AQt output
To

Maximum allowed temperature before a safety shutdown

If temperature exceeds this then the error is displayed on output Qe
Ts

Time before a safety shutdown occurs

After this time the sauna is turned off automatically
P

PWM period

Pulse width modulation period in seconds [s]
V

Gain

Gain in case of deviation
M

Type of AC input used

0 = Three-phase
1 = Single-phase
2 = 2 phase during condensation, 3 when used without condensor