Radio buttons (8x) and (16x)

This block allows you to select between one and eight (or sixteen on the larger block) outputs to be on.

Loxone Musterkoffer


The radio buttons blocks have 8 or 16 digital inputs and outputs. If a pulse occurs at an input the corresponding output is activated. For example a pulse on input I3 activates the output Q3.

Using the inputs + and - you can cycle up and down through the outputs. The number of outputs to be used can be defined with the parameter Ma. 

Using the input Als the output can be controlled directly, so if for example 5 is input at Als then the output 5 is activated. AQ outputs the currently selected output, for example if output 5 is active then the value of AQ is 5. If all the outputs are disabled then AQ has a value of 0.

To turn all the outputs off a pulse at R can be used or Als can be set to 0.

If Dis is enabled then all the inputs are locked, however you can still control the block through the user interface.

Examples of use:
Selecting different commands for controlling AV equipment, selecting switches for applications, mode selection etc.

User interface

Radio buttons user interface has different names for each output. To edit these double click on the block. 

The names will be displayed until the first blank name.




I1-I8 (I16) Trigger inputs Pulse activates outputs Q1-Q8 (Q16)  
+ Select next output Cycle forward through the outputs 0-8 (16)
- Select previous output Cycle backward through the outputs 0-8 (16)
Als Analogue input The value of Als will determine which output is activated, if Als is 4 output 4 will be active
R Reset Sets all the outputs to 0
Dis Disable Will lock all the inputs (but not the user interface)


Q1-Q8 (16) Digital outputs Controlled by a pulse at the inputs 11-18 (16)
AQ Currently active output Specifies the value of the active output. for example:. Q5 is active, AQ = 5  
RQ Reset output Sends out a pulse if reset or a double click is detected  


Ma Maximum number of outputs Defines the number of input/outputs that can be used. (Important when cycling through with + and -)
M All off included in cycle If M not active when cycling through with + after the last output Q1 is then activated again.