Loxone Touch Tree

How to setup your Loxone Touch Tree

Loxone Musterkoffer

Technical Specifications

  • Power supply: 24 VDC
  • Power consumption: 115mW ~
  • Temperature & humidity measurement *
  • 5 touch points
  • Optional click feedback when touched
  • Status LED
  • Temperature measuring range: -20 ... + 80 ° C
  • Temperature tolerance: +/- 0.5 ° C
  • Measuring range Humidity: 0 - 100%
  • Moisture tolerance: +/- 2% RH
  • Ambient temperature: 0 ... + 55 ° C
  • Dimensions: 55mm x 55mm without frame
  • Cable diameter 0.25-0.8 mm²
  • Stripped cable length: 5mm
  • Protection: IP20



Please note temperature and humidity is sensed through the touch trees closed housing which can mean a delay in sensing time. For the rapid detection of changes in the ambient humidity (eg. For ventilation control in the bathroom), we recommend a sensor with an open housing design as the Loxone Temperature & Humidity Sensor Air.


To commision the Touch tree connect the 24V power (orange/Orange-white terminals) and the Tree terminals (Green/Green-white terminals). The device will flash orange when connected.

To learn in the touch tree click on the Tree Extension and then click "Tree Search Device"

All connected tree devices will be listed in the search window.
Select the correct device in the search window and click “create". The Touch tree will now be listed in the periphery tree.
The following objects are available under the touch tree:
  • Combined key T5

  • Analog Input humidity

  • Analog Input temperature

It is possible to use each touch zone on the device as a separate digital output. Use the check boxes to activate this functionality.
The “acoustic feedback” check box is where audible feedback of a switch can be activated. If this is selected a short “click” will be heard at the switch when pressed.

Replace device

Replacing a device is easy via the Tree search window. Install the new device and connect power. Select the device in the Tree search window then click on the drop-down menu to find the device you wish to replace. Finally select “replace device” button and the new device will be added in its place. Be sure to save in the miniserver to commit these changes.

Touch Points

The touch points may be used in Loxone Config as digital inputs. Every touch point is a digital input.

For Press and Hold, you will need to set the 'Receive Timeout' properties of the Digital Input to 0.

Combined key T5

The T5 output combines all 5 of the digital outputs of the Touch tree. This is designed to speed up the programming of the Loxone standard.
The following functions are supported here:
  • Automatic blinds: inputs Cu (touch point 1) and Cd (touch point 4)

  • Light Control: Scene + (touch point 3)

  • Music Server Zone: inputs V + (touch point 2) and V- (touch point 5)

  • Central block control (double/triple click of centre key)

Connect the T5 output to the T5 input of the desired blocks.
In order to program and user-defined functions, ensure check boxes for inputs are activate in properties.